Flow rate calculators / Valves & flow measurement
Measure flow. Understand the conditions.
Required Valve Cv Calculator
Find a preliminary Cv for a specified nonchoked liquid flow and allocated pressure drop.
Your flow inputs
Your result
Ready to calculateEnter your values and press Calculate. The result will open on the calculation page.
Published references · Clear assumptions · No sign-up
The method
Formula and calculation steps
Required Cv = US GPM × √(specific gravity / pressure drop psi).
Find a preliminary Cv for a specified nonchoked liquid flow and allocated pressure drop.
- Choose a measurement plane and use compatible units for all inputs.
- Obtain appropriate product data or representative measurements for the stated model.
- Submit the form, then interpret the result with the assumptions and limits below.
No cavitation, flashing, viscosity or installation correction factors are selected.
Required Valve Cv calculation: inputs and interpretation
This inverse arithmetic does not select valve size or prove controllability. Available differential should be the amount assigned to the valve at the relevant operating point, and actual rangeability and authority require additional analysis.
Discharge and valve coefficients describe a specific device and test basis. The examples are not certified calibrations. Pressure-tap arrangement, density, Reynolds number and downstream conditions can change the relationship between a measured pressure difference and actual flow.
Continue with: Liquid Orifice Flow Calculator · Orifice Diameter from Flow Calculator · Venturi Flow Meter Calculator · Valve Cv Flow Calculator
Check the numbers
Required Valve Cv Calculator: calculated examples
These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.
Worked example with stated inputs
Required liquid flow = 20 US GPM; Available valve differential = 10 psi; Liquid specific gravity = 1 water-relative.
| Output | Computed result |
|---|---|
| Preliminary liquid Cv requirement | 6.324555 Cv |
How one input changes the answer
| Scenario | Changed input | Result |
|---|---|---|
| 5 US GPM | Required liquid flow | 1.581139 Cv |
| 10 US GPM | Required liquid flow | 3.162278 Cv |
| 15 US GPM | Required liquid flow | 4.743416 Cv |
| 20 US GPM | Required liquid flow | 6.324555 Cv |
| 30 US GPM | Required liquid flow | 9.486833 Cv |
| 40 US GPM | Required liquid flow | 12.649111 Cv |
| 60 US GPM | Required liquid flow | 18.973666 Cv |
Unchanged inputs use: Required liquid flow = 20 US GPM; Available valve differential = 10 psi; Liquid specific gravity = 1 water-relative. Results retain the model limitations described above.
Common questions
Does required Cv directly equal nominal valve diameter?
No. Different designs and travels can have different Cv at the same nominal size.
Can I choose a valve only from this result?
No. Check the full manufacturer sizing procedure and actual service conditions.
What happens at very small allocated pressure drop?
The simple required coefficient rises sharply; that does not make every valve suitable.
Does this use US or Imperial GPM?
US liquid gallons per minute.
Which assumptions should I verify?
Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.
Where are the formula sources?
Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.
Related calculators
Formula sources and references
References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.
- Emerson Control Valve Handbook, Chapter 5: liquid and gas sizing boundarieshttps://www.emerson.com/is/content/emerson/it/final-control/flow-controls/valves/documents/control-valve-handbook-en-3661206.pdf
- NIST SP 811 Appendix B.9: volume, mass and flow unit factorshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9