Hydrant Pitot Discharge Calculator

Estimate outlet water discharge using a stated pitot-pressure coefficient relationship.

Your flow inputs

inches
psi
ratio

Starting values are illustrative. Check units and assumptions below. Calculate submits your inputs to this site’s result page.

Reset

Your result

Ready to calculate

Enter your values and press Calculate. The result will open on the calculation page.

Published references · Clear assumptions · No sign-up

The method

Formula and calculation steps

Approximate US GPM = 29.83 × outlet coefficient × diameter(in)² × √pitot psi.

Estimate outlet water discharge using a stated pitot-pressure coefficient relationship.

  1. Choose a measurement plane and use compatible units for all inputs.
  2. Obtain appropriate product data or representative measurements for the stated model.
  3. Submit the form, then interpret the result with the assumptions and limits below.

Not a test-method approval, required-fire-flow calculation or equipment rating.

Hydrant Pitot Discharge calculation: inputs and interpretation

Pitot velocity pressure is not the static or residual water-main gauge reading. Outlet geometry and the measurement procedure determine the relevant coefficient. The rounded numerical factor follows the water velocity-pressure and US unit basis of the cited method.

A pump operates where its curve meets the system curve. The tools here isolate a stated energy, displacement or test relationship; they do not automatically select a pump or verify suction conditions, cavitation margin, protection or installation requirements.

Check the numbers

Hydrant Pitot Discharge Calculator: calculated examples

These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.

Worked example with stated inputs

Outlet internal diameter = 2.5 inches; Pitot velocity pressure = 20 psi; Outlet discharge coefficient = 0.9 ratio.

OutputComputed result
Pitot-coefficient discharge estimate750.396462 US GPM

How one input changes the answer

ScenarioChanged inputResult
5 psiPitot velocity pressure375.198231 US GPM
10 psiPitot velocity pressure530.610427 US GPM
15 psiPitot velocity pressure649.862399 US GPM
20 psiPitot velocity pressure750.396462 US GPM
30 psiPitot velocity pressure919.044219 US GPM
40 psiPitot velocity pressure1,061.220854 US GPM
60 psiPitot velocity pressure1,299.724799 US GPM

Unchanged inputs use: Outlet internal diameter = 2.5 inches; Pitot velocity pressure = 20 psi; Outlet discharge coefficient = 0.9 ratio. Results retain the model limitations described above.

Common questions

Can I enter main residual pressure as pitot pressure?

No. Those are different measurements in the test method.

Is the coefficient always 0.9?

No. Obtain a value justified for the actual outlet shape and test arrangement.

Can I total several flowing outlets?

Calculate each properly measured outlet on a compatible basis and add the discharges.

Does this certify available fire flow at a target residual?

No. Target-residual extrapolation and test acceptance are separate issues.

Which assumptions should I verify?

Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.

Where are the formula sources?

Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.

Formula sources and references

References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.

  • NFPA 291 public input report: hydrant residual-pressure flow relationship; historical method reference, not current compliance certificationhttps://www.nfpa.org/api/files?path=%2Ffiles%2FAboutTheCodes%2F291%2F291_A2021_AUT_PRI_PIReport.pdf
  • US DOE Fundamentals Handbook, Thermodynamics, Heat Transfer and Fluid Flow, Volume 3https://www.energy.gov/sites/default/files/2026-04/DOE-HDBK-1012-92_VOL3.pdf