Flow rate calculators / Pumps & water systems
Measure flow. Understand the conditions.
Hydrant Pitot Discharge Calculator
Estimate outlet water discharge using a stated pitot-pressure coefficient relationship.
Your flow inputs
Your result
Ready to calculateEnter your values and press Calculate. The result will open on the calculation page.
Published references · Clear assumptions · No sign-up
The method
Formula and calculation steps
Approximate US GPM = 29.83 × outlet coefficient × diameter(in)² × √pitot psi.
Estimate outlet water discharge using a stated pitot-pressure coefficient relationship.
- Choose a measurement plane and use compatible units for all inputs.
- Obtain appropriate product data or representative measurements for the stated model.
- Submit the form, then interpret the result with the assumptions and limits below.
Not a test-method approval, required-fire-flow calculation or equipment rating.
Hydrant Pitot Discharge calculation: inputs and interpretation
Pitot velocity pressure is not the static or residual water-main gauge reading. Outlet geometry and the measurement procedure determine the relevant coefficient. The rounded numerical factor follows the water velocity-pressure and US unit basis of the cited method.
A pump operates where its curve meets the system curve. The tools here isolate a stated energy, displacement or test relationship; they do not automatically select a pump or verify suction conditions, cavitation margin, protection or installation requirements.
Continue with: Pump Power Calculator · Pump Flow from Power Calculator · Pump Affinity Laws Calculator · Displacement Pump Flow Calculator
Check the numbers
Hydrant Pitot Discharge Calculator: calculated examples
These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.
Worked example with stated inputs
Outlet internal diameter = 2.5 inches; Pitot velocity pressure = 20 psi; Outlet discharge coefficient = 0.9 ratio.
| Output | Computed result |
|---|---|
| Pitot-coefficient discharge estimate | 750.396462 US GPM |
How one input changes the answer
| Scenario | Changed input | Result |
|---|---|---|
| 5 psi | Pitot velocity pressure | 375.198231 US GPM |
| 10 psi | Pitot velocity pressure | 530.610427 US GPM |
| 15 psi | Pitot velocity pressure | 649.862399 US GPM |
| 20 psi | Pitot velocity pressure | 750.396462 US GPM |
| 30 psi | Pitot velocity pressure | 919.044219 US GPM |
| 40 psi | Pitot velocity pressure | 1,061.220854 US GPM |
| 60 psi | Pitot velocity pressure | 1,299.724799 US GPM |
Unchanged inputs use: Outlet internal diameter = 2.5 inches; Pitot velocity pressure = 20 psi; Outlet discharge coefficient = 0.9 ratio. Results retain the model limitations described above.
Common questions
Can I enter main residual pressure as pitot pressure?
No. Those are different measurements in the test method.
Is the coefficient always 0.9?
No. Obtain a value justified for the actual outlet shape and test arrangement.
Can I total several flowing outlets?
Calculate each properly measured outlet on a compatible basis and add the discharges.
Does this certify available fire flow at a target residual?
No. Target-residual extrapolation and test acceptance are separate issues.
Which assumptions should I verify?
Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.
Where are the formula sources?
Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.
Related calculators
Formula sources and references
References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.
- NFPA 291 public input report: hydrant residual-pressure flow relationship; historical method reference, not current compliance certificationhttps://www.nfpa.org/api/files?path=%2Ffiles%2FAboutTheCodes%2F291%2F291_A2021_AUT_PRI_PIReport.pdf
- US DOE Fundamentals Handbook, Thermodynamics, Heat Transfer and Fluid Flow, Volume 3https://www.energy.gov/sites/default/files/2026-04/DOE-HDBK-1012-92_VOL3.pdf