Sensible Heat Airflow Calculator

Calculate a sensible-airflow requirement from explicit air properties and temperature difference.

Your flow inputs

kW
kg/m³
J/kg/K
K

Starting values are illustrative. Check units and assumptions below. Calculate submits your inputs to this site’s result page.

Reset

Your result

Ready to calculate

Enter your values and press Calculate. The result will open on the calculation page.

Published references · Clear assumptions · No sign-up

The method

Formula and calculation steps

Actual volume flow = sensible heat W / (density × specific heat × temperature change).

Calculate a sensible-airflow requirement from explicit air properties and temperature difference.

  1. Choose a measurement plane and use compatible units for all inputs.
  2. Obtain appropriate product data or representative measurements for the stated model.
  3. Submit the form, then interpret the result with the assumptions and limits below.

No ventilation minimum, coil selection or humidity-control calculation is supplied.

Sensible Heat Airflow calculation: inputs and interpretation

This is the energy-balance form behind many CFM and temperature-rise approximations. It holds density and specific heat fixed and uses only sensible heat. Moisture removal, latent heat, equipment bypass and psychrometric state changes require a fuller model.

An airflow estimate does not certify indoor air quality or determine a code-required ventilation rate. Use the actual operating fan point, measurement plane and air density. Filter loading, duct losses, leakage and balancing can change delivered airflow.

Check the numbers

Sensible Heat Airflow Calculator: calculated examples

These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.

Worked example with stated inputs

Sensible thermal load = 5 kW; Applicable air density = 1.2 kg/m³; Specific heat = 1006 J/kg/K; Positive air temperature change = 10 K.

OutputComputed result
Sensible-load airflow877.601062 CFM
Volume flow SI0.414182 m³/s
Volume flow hourly1,491.053678 m³/h
US liquid flow6,564.911838 US GPM
Cubic feet per minute877.601062 CFM

How one input changes the answer

ScenarioChanged inputResult
1.25 kWSensible thermal load219.400265 CFM
2.5 kWSensible thermal load438.800531 CFM
3.75 kWSensible thermal load658.200796 CFM
5 kWSensible thermal load877.601062 CFM
7.5 kWSensible thermal load1,316.401593 CFM
10 kWSensible thermal load1,755.202123 CFM
15 kWSensible thermal load2,632.803185 CFM

Unchanged inputs use: Sensible thermal load = 5 kW; Applicable air density = 1.2 kg/m³; Specific heat = 1006 J/kg/K; Positive air temperature change = 10 K. Results retain the model limitations described above.

Common questions

Can I use the familiar 1.08 CFM formula?

That is an approximate US-unit shortcut with property assumptions. This tool exposes density and specific heat instead.

Does it include latent cooling?

No. The load must be the sensible portion matching the stated temperature change.

Can temperature difference be in °C?

A temperature difference of one °C has the same magnitude as one K; absolute temperatures are a different issue.

Does this determine required fresh air?

No. Heat-removal airflow and outdoor-air requirements answer different questions.

Which assumptions should I verify?

Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.

Where are the formula sources?

Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.

Formula sources and references

References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.

  • US DOE Fundamentals Handbook, Thermodynamics, Heat Transfer and Fluid Flow, Volume 2: sensible heat and LMTDhttps://archives.standards.doxcelerate.com/documents/doe-hdbk-1012-2-92-thermodynamics-heat-transfer-and-fluid-flow-volume-2-of-3
  • NIST SP 811 Appendix B.9: volume, mass and flow unit factorshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9