Flow rate calculators / Airflow & ventilation
Measure flow. Understand the conditions.
Sensible Heat Airflow Calculator
Calculate a sensible-airflow requirement from explicit air properties and temperature difference.
Your flow inputs
Your result
Ready to calculateEnter your values and press Calculate. The result will open on the calculation page.
Published references · Clear assumptions · No sign-up
The method
Formula and calculation steps
Actual volume flow = sensible heat W / (density × specific heat × temperature change).
Calculate a sensible-airflow requirement from explicit air properties and temperature difference.
- Choose a measurement plane and use compatible units for all inputs.
- Obtain appropriate product data or representative measurements for the stated model.
- Submit the form, then interpret the result with the assumptions and limits below.
No ventilation minimum, coil selection or humidity-control calculation is supplied.
Sensible Heat Airflow calculation: inputs and interpretation
This is the energy-balance form behind many CFM and temperature-rise approximations. It holds density and specific heat fixed and uses only sensible heat. Moisture removal, latent heat, equipment bypass and psychrometric state changes require a fuller model.
An airflow estimate does not certify indoor air quality or determine a code-required ventilation rate. Use the actual operating fan point, measurement plane and air density. Filter loading, duct losses, leakage and balancing can change delivered airflow.
Continue with: Airflow CFM Calculator · Air Changes to CFM Calculator · Bathroom Exhaust Fan Flow Calculator · Fan Power Calculator
Check the numbers
Sensible Heat Airflow Calculator: calculated examples
These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.
Worked example with stated inputs
Sensible thermal load = 5 kW; Applicable air density = 1.2 kg/m³; Specific heat = 1006 J/kg/K; Positive air temperature change = 10 K.
| Output | Computed result |
|---|---|
| Sensible-load airflow | 877.601062 CFM |
| Volume flow SI | 0.414182 m³/s |
| Volume flow hourly | 1,491.053678 m³/h |
| US liquid flow | 6,564.911838 US GPM |
| Cubic feet per minute | 877.601062 CFM |
How one input changes the answer
| Scenario | Changed input | Result |
|---|---|---|
| 1.25 kW | Sensible thermal load | 219.400265 CFM |
| 2.5 kW | Sensible thermal load | 438.800531 CFM |
| 3.75 kW | Sensible thermal load | 658.200796 CFM |
| 5 kW | Sensible thermal load | 877.601062 CFM |
| 7.5 kW | Sensible thermal load | 1,316.401593 CFM |
| 10 kW | Sensible thermal load | 1,755.202123 CFM |
| 15 kW | Sensible thermal load | 2,632.803185 CFM |
Unchanged inputs use: Sensible thermal load = 5 kW; Applicable air density = 1.2 kg/m³; Specific heat = 1006 J/kg/K; Positive air temperature change = 10 K. Results retain the model limitations described above.
Common questions
Can I use the familiar 1.08 CFM formula?
That is an approximate US-unit shortcut with property assumptions. This tool exposes density and specific heat instead.
Does it include latent cooling?
No. The load must be the sensible portion matching the stated temperature change.
Can temperature difference be in °C?
A temperature difference of one °C has the same magnitude as one K; absolute temperatures are a different issue.
Does this determine required fresh air?
No. Heat-removal airflow and outdoor-air requirements answer different questions.
Which assumptions should I verify?
Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.
Where are the formula sources?
Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.
Related calculators
Formula sources and references
References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.
- US DOE Fundamentals Handbook, Thermodynamics, Heat Transfer and Fluid Flow, Volume 2: sensible heat and LMTDhttps://archives.standards.doxcelerate.com/documents/doe-hdbk-1012-2-92-thermodynamics-heat-transfer-and-fluid-flow-volume-2-of-3
- NIST SP 811 Appendix B.9: volume, mass and flow unit factorshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9