Flow Rate CalculatorLiquid, gas & engineering tools

Flow rate calculators / Airflow & ventilation

Measure flow. Understand the conditions.

Airflow CFM Calculator

Calculate imperial rectangular-duct airflow from clear dimensions and an average velocity traverse.

Your flow inputs

inches
inches
ft/min

Starting values are illustrative. Check units and assumptions below. Calculate submits your inputs to this site’s result page.

Reset

Your result

Ready to calculate

Enter your values and press Calculate. The result will open on the calculation page.

Published references · Clear assumptions · No sign-up

The method

Formula and calculation steps

CFM = velocity FPM × (width inches × height inches / 144).

Calculate imperial rectangular-duct airflow from clear dimensions and an average velocity traverse.

  1. Choose a measurement plane and use compatible units for all inputs.
  2. Obtain appropriate product data or representative measurements for the stated model.
  3. Submit the form, then interpret the result with the assumptions and limits below.

Not a fan-rating, standard-volume correction or building ventilation approval.

Airflow CFM calculation: inputs and interpretation

The area conversion uses 144 square inches per square foot. The reading must represent mean velocity at that clear section. A centerline reading in a distorted profile, or the exterior grille dimensions rather than effective free area, can misstate delivered airflow.

An airflow estimate does not certify indoor air quality or determine a code-required ventilation rate. Use the actual operating fan point, measurement plane and air density. Filter loading, duct losses, leakage and balancing can change delivered airflow.

Check the numbers

Airflow CFM Calculator: calculated examples

These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.

Worked example with stated inputs

Clear duct width = 12 inches; Clear duct height = 8 inches; Area-averaged air velocity = 800 ft/min.

OutputComputed result
Local rectangular-duct airflow533.333333 CFM
Volume flow SI0.251705 m³/s
Volume flow hourly906.139091 m³/h
US liquid flow3,989.61039 US GPM
Cubic feet per minute533.333333 CFM

How one input changes the answer

ScenarioChanged inputResult
200 ft/minArea-averaged air velocity133.333333 CFM
400 ft/minArea-averaged air velocity266.666667 CFM
600 ft/minArea-averaged air velocity400 CFM
800 ft/minArea-averaged air velocity533.333333 CFM
1200 ft/minArea-averaged air velocity800 CFM
1600 ft/minArea-averaged air velocity1,066.666667 CFM
2400 ft/minArea-averaged air velocity1,600 CFM

Unchanged inputs use: Clear duct width = 12 inches; Clear duct height = 8 inches; Area-averaged air velocity = 800 ft/min. Results retain the model limitations described above.

Common questions

Can I convert FPM to CFM without area?

No. Flow is average velocity multiplied by the free section area.

Does CFM here mean SCFM?

No. It is local actual geometric volume flow unless a reference correction is explicitly made.

Can I use grille face dimensions?

Only if they represent the correct effective measurement area; blockage and free-area definitions matter.

Does this calculate fan output from HP?

No. That needs a flow-pressure performance relationship.

What is the CFM calculation formula for ducting or an AHU?

For an actual measurement plane, CFM equals clear area in square feet times mean velocity in feet per minute. This page applies that section relationship. Selecting an AHU or ventilation requirement also needs pressure, outdoor-air requirements and project data.

Can I convert FPM, ft/min or m/s to CFM without duct size?

No. Velocity is distance per time; CFM is volume per time. Supply the relevant clear cross-sectional area, then multiply. Obstructions and nonuniform profiles can make external duct dimensions or a single point reading unsuitable.

Which assumptions should I verify?

Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.

Where are the formula sources?

Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.

Formula sources and references

References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.

  • US Bureau of Reclamation Water Measurement Manual, 2.4: discharge, area and velocityhttps://www.usbr.gov/tsc/techreferences/mands/wmm/chap02_04.html
  • US Department of Energy: Improving Fan System Performance, pressure-flow power and fan lawshttps://www.energy.gov/sites/default/files/2014/05/f16/fan_sourcebook.pdf