Flow Rate CalculatorLiquid, gas & engineering tools

Flow rate calculators / Airflow & ventilation

Measure flow. Understand the conditions.

Fan Flow from Power Calculator

Estimate an air-volume flow from a stated low-pressure fan energy balance.

Your flow inputs

kW
%
Pa

Starting values are illustrative. Check units and assumptions below. Calculate submits your inputs to this site’s result page.

Reset

Your result

Ready to calculate

Enter your values and press Calculate. The result will open on the calculation page.

Published references · Clear assumptions · No sign-up

The method

Formula and calculation steps

Actual Q m³/s = input W × efficiency / pressure increase Pa.

Estimate an air-volume flow from a stated low-pressure fan energy balance.

  1. Choose a measurement plane and use compatible units for all inputs.
  2. Obtain appropriate product data or representative measurements for the stated model.
  3. Submit the form, then interpret the result with the assumptions and limits below.

Not an air-compressor horsepower conversion or proof that a real fan curve reaches the calculated point.

Fan Flow from Power calculation: inputs and interpretation

This is a conditional inverse relationship, not a universal HP-to-CFM conversion. Input power, the pressure definition and its corresponding efficiency must describe the same operating point. A motor nameplate maximum does not establish actual consumed power.

An airflow estimate does not certify indoor air quality or determine a code-required ventilation rate. Use the actual operating fan point, measurement plane and air density. Filter loading, duct losses, leakage and balancing can change delivered airflow.

Check the numbers

Fan Flow from Power Calculator: calculated examples

These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.

Worked example with stated inputs

Actual input power = 1 kW; Matching fan-system efficiency = 60 %; Specified pressure increase = 250 Pa.

OutputComputed result
Conditional fan energy-balance airflow5,085.312008 CFM
Volume flow SI2.4 m³/s
Volume flow hourly8,640 m³/h
US liquid flow38,040.77554 US GPM
Cubic feet per minute5,085.312008 CFM

How one input changes the answer

ScenarioChanged inputResult
0.25 kWActual input power1,271.328002 CFM
0.5 kWActual input power2,542.656004 CFM
0.75 kWActual input power3,813.984006 CFM
1 kWActual input power5,085.312008 CFM
1.5 kWActual input power7,627.968012 CFM
2 kWActual input power10,170.624016 CFM
3 kWActual input power15,255.936024 CFM

Unchanged inputs use: Actual input power = 1 kW; Matching fan-system efficiency = 60 %; Specified pressure increase = 250 Pa. Results retain the model limitations described above.

Common questions

Can I use 3 HP to find exhaust-fan CFM?

Convert actual mechanical or electrical power with the matching efficiency and specify pressure; HP alone is insufficient.

Can this convert compressor kW to CFM?

Not as a complete high-pressure compressor model. Pressure ratio and thermodynamics require more information.

Does a lower pressure imply greater modeled flow?

At fixed supplied power and efficiency this inverse equation does, but a real fan’s curve and limits still control.

Can I compare free-air ratings?

Only when the rating boundary matches the intended installed condition.

Can I convert CFM to electrical kW or kW to CFM?

Not as a unit conversion. This low-pressure fan relation also needs pressure rise and a consistent total efficiency. A compressor requires a different thermodynamic and performance model; motor rating alone does not establish delivered air.

Which assumptions should I verify?

Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.

Where are the formula sources?

Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.

Formula sources and references

References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.

  • US Department of Energy: Improving Fan System Performance, pressure-flow power and fan lawshttps://www.energy.gov/sites/default/files/2014/05/f16/fan_sourcebook.pdf
  • US DOE Fundamentals Handbook, Thermodynamics, Heat Transfer and Fluid Flow, Volume 3https://www.energy.gov/sites/default/files/2026-04/DOE-HDBK-1012-92_VOL3.pdf