Flow rate calculators / Airflow & ventilation
Measure flow. Understand the conditions.
Fan Power Calculator
Estimate air power and input power at an explicitly defined fan pressure boundary.
Your flow inputs
Your result
Ready to calculateEnter your values and press Calculate. The result will open on the calculation page.
Published references · Clear assumptions · No sign-up
The method
Formula and calculation steps
Air power W = actual m³/s × pressure increase Pa; input W = air power / matching efficiency.
Estimate air power and input power at an explicitly defined fan pressure boundary.
- Choose a measurement plane and use compatible units for all inputs.
- Obtain appropriate product data or representative measurements for the stated model.
- Submit the form, then interpret the result with the assumptions and limits below.
Not a fan curve, compressor thermodynamic model or motor selection.
Fan Power calculation: inputs and interpretation
State whether the pressure is static or total and use an efficiency on the same basis. Motor and drive losses must be included in efficiency if the desired output is electrical input. Actual airflow must match the density and operating condition of the measured pressure.
An airflow estimate does not certify indoor air quality or determine a code-required ventilation rate. Use the actual operating fan point, measurement plane and air density. Filter loading, duct losses, leakage and balancing can change delivered airflow.
Continue with: Airflow CFM Calculator · Air Changes to CFM Calculator · Bathroom Exhaust Fan Flow Calculator · Fan Flow from Power Calculator
Check the numbers
Fan Power Calculator: calculated examples
These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.
Worked example with stated inputs
Actual airflow = 1000 CFM; Chosen pressure increase = 250 Pa; Pressure-boundary-to-input efficiency = 60 %.
| Output | Computed result |
|---|---|
| Fan input at chosen pressure/efficiency boundary | 0.196645 kW |
| Air power | 117.986861 W |
| Mechanical HP equivalent | 0.263705 HP |
How one input changes the answer
| Scenario | Changed input | Result |
|---|---|---|
| 250 CFM | Actual airflow | 0.049161 kW |
| 500 CFM | Actual airflow | 0.098322 kW |
| 750 CFM | Actual airflow | 0.147484 kW |
| 1000 CFM | Actual airflow | 0.196645 kW |
| 1500 CFM | Actual airflow | 0.294967 kW |
| 2000 CFM | Actual airflow | 0.39329 kW |
| 3000 CFM | Actual airflow | 0.589934 kW |
Unchanged inputs use: Actual airflow = 1000 CFM; Chosen pressure increase = 250 Pa; Pressure-boundary-to-input efficiency = 60 %. Results retain the model limitations described above.
Common questions
Can I convert airflow to horsepower?
Only after providing pressure and a suitable efficiency. CFM alone has no unique power value.
Does a fan’s rated HP determine CFM?
No. The operating point and pressure-flow curve matter.
Is static efficiency interchangeable with total efficiency?
No. Use a pressure and efficiency definition that match.
Can it size a high-pressure compressor?
No. Compressible compression work requires a thermodynamic model beyond Q×small pressure increase.
Which assumptions should I verify?
Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.
Where are the formula sources?
Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.
Related calculators
Formula sources and references
References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.
- US Department of Energy: Improving Fan System Performance, pressure-flow power and fan lawshttps://www.energy.gov/sites/default/files/2014/05/f16/fan_sourcebook.pdf
- US DOE Fundamentals Handbook, Thermodynamics, Heat Transfer and Fluid Flow, Volume 3https://www.energy.gov/sites/default/files/2026-04/DOE-HDBK-1012-92_VOL3.pdf