Hood Face Velocity Airflow Calculator

Calculate the volume flow corresponding to a specified mean velocity across a rectangular hood opening.

Your flow inputs

ft
ft
ft/min

Starting values are illustrative. Check units and assumptions below. Calculate submits your inputs to this site’s result page.

Reset

Your result

Ready to calculate

Enter your values and press Calculate. The result will open on the calculation page.

Published references · Clear assumptions · No sign-up

The method

Formula and calculation steps

CFM through clear opening = opening width ft × height ft × average face velocity FPM.

Calculate the volume flow corresponding to a specified mean velocity across a rectangular hood opening.

  1. Choose a measurement plane and use compatible units for all inputs.
  2. Obtain appropriate product data or representative measurements for the stated model.
  3. Submit the form, then interpret the result with the assumptions and limits below.

Does not size a kitchen range hood or laboratory hood to a code, containment or exposure requirement.

Hood Face Velocity Airflow calculation: inputs and interpretation

The velocity input is a selected criterion, not a universal capture requirement. Average face flow, source capture at a distance and a certified hood containment test are different concepts. Use actual clear area and a representative measured velocity profile.

An airflow estimate does not certify indoor air quality or determine a code-required ventilation rate. Use the actual operating fan point, measurement plane and air density. Filter loading, duct losses, leakage and balancing can change delivered airflow.

Check the numbers

Hood Face Velocity Airflow Calculator: calculated examples

These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.

Worked example with stated inputs

Clear opening width = 3 ft; Clear opening height = 2 ft; Chosen average face velocity = 100 ft/min.

OutputComputed result
Chosen face-velocity opening flow600 CFM

How one input changes the answer

ScenarioChanged inputResult
25 ft/minChosen average face velocity150 CFM
50 ft/minChosen average face velocity300 CFM
75 ft/minChosen average face velocity450 CFM
100 ft/minChosen average face velocity600 CFM
150 ft/minChosen average face velocity900 CFM
200 ft/minChosen average face velocity1,200 CFM
300 ft/minChosen average face velocity1,800 CFM

Unchanged inputs use: Clear opening width = 3 ft; Clear opening height = 2 ft; Chosen average face velocity = 100 ft/min. Results retain the model limitations described above.

Common questions

Does face velocity prove contaminant capture?

No. Source position, cross-drafts, hood geometry and actual containment behavior also matter.

Is the default velocity a recommended minimum?

No. It is an illustrative calculation input.

Can I use the external hood dimensions?

Use the actual clear opening relevant to the velocity measurement.

Does it calculate static pressure?

No. Duct, filter and equipment resistance must be assessed separately.

Which assumptions should I verify?

Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.

Where are the formula sources?

Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.

Formula sources and references

References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.

  • US Department of Energy: Improving Fan System Performance, pressure-flow power and fan lawshttps://www.energy.gov/sites/default/files/2014/05/f16/fan_sourcebook.pdf
  • US Bureau of Reclamation Water Measurement Manual, 2.4: discharge, area and velocityhttps://www.usbr.gov/tsc/techreferences/mands/wmm/chap02_04.html