Flow rate calculators / Airflow & ventilation
Measure flow. Understand the conditions.
Fan Affinity Laws Calculator
Scale a reference fan point for a speed change under stated similarity assumptions.
Your flow inputs
Your result
Ready to calculateEnter your values and press Calculate. The result will open on the calculation page.
Published references · Clear assumptions · No sign-up
The method
Formula and calculation steps
For similar operation at unchanged density and geometry: flow∝RPM, pressure∝RPM², power∝RPM³.
Scale a reference fan point for a speed change under stated similarity assumptions.
- Choose a measurement plane and use compatible units for all inputs.
- Obtain appropriate product data or representative measurements for the stated model.
- Submit the form, then interpret the result with the assumptions and limits below.
Does not approve an overspeed condition or substitute for manufacturer performance data.
Fan Affinity Laws calculation: inputs and interpretation
Fan laws describe comparable operating points, not an automatic installed-flow prediction. The real system resistance curve determines the new operating point. Changes in air density, efficiency, stall region or mechanical limits can invalidate a simple scale-up.
An airflow estimate does not certify indoor air quality or determine a code-required ventilation rate. Use the actual operating fan point, measurement plane and air density. Filter loading, duct losses, leakage and balancing can change delivered airflow.
Continue with: Airflow CFM Calculator · Air Changes to CFM Calculator · Bathroom Exhaust Fan Flow Calculator · Fan Power Calculator
Check the numbers
Fan Affinity Laws Calculator: calculated examples
These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.
Worked example with stated inputs
Original actual airflow = 1000 CFM; Original pressure increase = 250 Pa; Original input power = 0.5 kW; Original speed = 1000 RPM; New speed = 1200 RPM.
| Output | Computed result |
|---|---|
| Similarity-scaled fan flow | 1,200 CFM |
| Scaled pressure | 360 Pa |
| Scaled power | 0.864 kW |
| Speed ratio | 1.2 ratio |
How one input changes the answer
| Scenario | Changed input | Result |
|---|---|---|
| 300 RPM | New speed | 300 CFM |
| 600 RPM | New speed | 600 CFM |
| 900 RPM | New speed | 900 CFM |
| 1200 RPM | New speed | 1,200 CFM |
| 1800 RPM | New speed | 1,800 CFM |
| 2400 RPM | New speed | 2,400 CFM |
| 3600 RPM | New speed | 3,600 CFM |
Unchanged inputs use: Original actual airflow = 1000 CFM; Original pressure increase = 250 Pa; Original input power = 0.5 kW; Original speed = 1000 RPM; New speed = 1200 RPM. Results retain the model limitations described above.
Common questions
Does halving RPM halve power?
Ideal similarity power is one eighth at half speed, under the appropriate assumptions.
Does a new curve point guarantee the room airflow?
No. The system pressure-loss relationship must also be considered.
Can I scale for different air density here?
This version holds density fixed; it has no density-ratio correction input.
Is every scaled speed permitted?
No. Mechanical, motor and operating-region limits must be checked independently.
Can I convert CFM to RPM?
No fixed conversion exists. With a valid reference speed and flow at similar conditions, the fan affinity relationship estimates the corresponding similar-point flow. It does not locate the operating point of an arbitrary duct system.
Which assumptions should I verify?
Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.
Where are the formula sources?
Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.
Related calculators
Formula sources and references
References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.
- US Department of Energy: Improving Fan System Performance, pressure-flow power and fan lawshttps://www.energy.gov/sites/default/files/2014/05/f16/fan_sourcebook.pdf