Counterflow Heat Exchanger LMTD Calculator
Calculate a positive counterflow logarithmic mean temperature difference and an ideal UA-based duty.
Your flow inputs
Your result
Ready to calculateEnter your values and press Calculate. The result will open on the calculation page.
Published references · Clear assumptions · No sign-up
The method
Formula and calculation steps
Counterflow ΔT₁=hot inlet−cold outlet; ΔT₂=hot outlet−cold inlet; LMTD=(ΔT₁−ΔT₂)/ln(ΔT₁/ΔT₂).
Calculate a positive counterflow logarithmic mean temperature difference and an ideal UA-based duty.
- Choose a measurement plane and use compatible units for all inputs.
- Obtain appropriate product data or representative measurements for the stated model.
- Submit the form, then interpret the result with the assumptions and limits below.
Not a complete heat-exchanger design, pinch analysis or vendor rating.
Counterflow Heat Exchanger LMTD calculation: inputs and interpretation
Both terminal temperature differences must be positive for this form. When they are equal, the limiting logarithmic mean is that common value. A multipass exchanger may need a correction factor, and supplied UA and temperatures must be mutually consistent with stream energy balances.
The inputs must describe the actual process boundary. Fluid properties, temperature or enthalpy change and equipment behavior can vary during operation. The displayed equations are preliminary calculations and do not implement proprietary equipment performance maps.
Continue with: Heating & Chilled Water Flow Calculator · Water Flow Heat Transfer Calculator · Steam Mass Flow from Heat Duty Calculator · Carburetor CFM Calculator
Check the numbers
Counterflow Heat Exchanger LMTD Calculator: calculated examples
These are computed scenarios using the same server calculation as the form. They are not manufacturer ratings or prescribed design values.
Worked example with stated inputs
Hot inlet temperature = 80 °C; Hot outlet temperature = 50 °C; Cold inlet temperature = 20 °C; Cold outlet temperature = 40 °C; Overall UA = 1000 W/K.
| Output | Computed result |
|---|---|
| Counterflow logarithmic mean temperature difference | 34.760595 K |
| Ideal UA-based duty | 34.760595 kW |
| Terminal difference 1 | 40 K |
| Terminal difference 2 | 30 K |
How one input changes the answer
| Scenario | Changed input | Result |
|---|---|---|
| 250 W/K | Overall UA | 34.760595 K |
| 500 W/K | Overall UA | 34.760595 K |
| 750 W/K | Overall UA | 34.760595 K |
| 1000 W/K | Overall UA | 34.760595 K |
| 1500 W/K | Overall UA | 34.760595 K |
| 2000 W/K | Overall UA | 34.760595 K |
| 3000 W/K | Overall UA | 34.760595 K |
Unchanged inputs use: Hot inlet temperature = 80 °C; Hot outlet temperature = 50 °C; Cold inlet temperature = 20 °C; Cold outlet temperature = 40 °C; Overall UA = 1000 W/K. Results retain the model limitations described above.
Common questions
What happens when both terminal differences are equal?
The LMTD limit equals the common temperature difference rather than dividing zero by zero.
Can I use the parallel-flow terminal pairing here?
No. This page explicitly uses the counterflow end pairing.
Does UA times LMTD prove feasible outlet temperatures?
No. Stream heat-capacity rates and full energy balances must also agree.
Can I use a negative terminal difference?
This positive-difference model rejects that input; another analysis is required.
Which assumptions should I verify?
Check every unit, the observation period and the physical or reference-state boundary stated above. Starting inputs and computed examples are illustrative scenarios, not recommended settings, certified capacities or universal standards.
Where are the formula sources?
Published method and unit references appear at the bottom of this page as plain-text addresses. Computed tables use the same server calculation as the form. No external content-data file is needed at runtime.
Related calculators
Formula sources and references
References support the underlying methods and units. Chosen example inputs are not universal recommendations, current tariffs or proprietary test results.
- US DOE Fundamentals Handbook, Thermodynamics, Heat Transfer and Fluid Flow, Volume 2: sensible heat and LMTDhttps://archives.standards.doxcelerate.com/documents/doe-hdbk-1012-2-92-thermodynamics-heat-transfer-and-fluid-flow-volume-2-of-3
- NIST SP 811 Appendix B.9: volume, mass and flow unit factorshttps://www.nist.gov/pml/special-publication-811/nist-guide-si-appendix-b-conversion-factors/nist-guide-si-appendix-b9